2. The
insulation resistance and dielectric strength
(1)
Insulation resistance: Each independent electrical circuit for insulation
resistance between ground and the circuit should be more than 2M
(2)
Dielectric strength: each unit independent electrical circuit for the circuit
between ground and should be able to withstand AC test voltage 1min, should be
no breakdown or flicker.
Circuit
voltage test voltage
<100V
750V
≥100V 1440V
3. The
phase sequence requirements. Diesel generator set control panel terminals phase
sequence from the front control panel should be under ordering from left to
right or from top to.
4. ready
to run diesel generators to maintain the state requirements. The crew should have
heating device to ensure its emergency oil temperature during startup and fast
load, coolant temperature not lower than 15 ℃